Residential H&V - 60Hz R22 &R410A
Rev.: 22 Dec, 2008
climatemaster.com
Water
Connection End
Return Air
Remove Screws
Water
Connection End
Return Air
Rotate
Move to Side
Side Discharge
Return Air
Water
Connection End
Discharge Air
Drain
Back Discharge
Replace Screws
Water
Connection End
Supply Duct
Return Air
Water
Connection End
Drain
Return Air
Discharge Air
Side Discharge
Back Discharge
Overview
Horizontal units can be eld converted between side
(straight) and back (end) discharge using the instructions
below.
Note: It is not possible to eld convert return air between
left or right return models due to the necessity of
refrigeration copper piping changes.
Preparation
It is best to eld convert the unit on the ground before
hanging. If the unit is already hung it should be taken down
for the eld conversion.
Side to Back Discharge Conversion
1.
Place unit in well lit area. Remove the screws as shown in
Figure 4 to free top panel and discharge panel.
2. Lift out the access panel and set aside. Lift and rotate
the discharge panel to the other position as shown,
being careful with the blower wiring.
3.
Check blower wire routing and connections for tension or
contact with sheet metal edges. Reroute if necessary.
4. Check refrigerant tubing for contact with
other components.
5. Reinstall top panel and screws noting that the location
for some screws will have changed.
6. Manually spin the fan wheel to insure that the wheel is
not rubbing or obstructed.
7. Replace access panels.
Back to Side Discharge Conversion
If the discharge is changed from back to side, use above
instruction noting that illustrations will be reversed.
Left vs. Right Return
It is not possible to eld convert return air between left or
right return models due to the necessity of refrigeration
copper piping changes. However, the conversion process
of side to back or back to side discharge for either right
or left return con guration is the same. In some cases, it
may be possible to rotate the entire unit 180 degrees if the
return air connection needs to be on the opposite side.
Note that rotating the unit will move the piping to the other
end of the unit.
Field Conversion of Air Discharge
Figure 5: Right Return Side to Back
Figure 4: Left Return Side to Back
Section 10 - Packaged IOM 7 4/24/09 3:16:49 PM