ClimateMaster DC Series Installation Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
Residential H&V - 60Hz R22 &R410A
Rev.: 22 Dec, 2008
10
Water-Source Heating and Cooling Systems
Vertical Installation
Sound Attenuation for Vertical Units
Sound attenuation is achieved by enclosing the unit within a
small mechanical room or a closet. Additional measures for
sound control include the following:
1. Mount the unit so that the return air inlet is 90° to the
return air grille. Refer to Figure 9. Install a sound baf e
as illustrated to reduce line-of sight sound transmitted
through return air grilles.
2.
Mount the unit on a rubber or neoprene isolation pad to
minimize vibration transmission to the building structure.
Figure 9: Vertical Sound Attenuation
Condensate Piping – Vertical Units
Vertical units utilize a condensate hose inside the cabinet as
a trapping loop; therefore an external trap is not necessary.
Figure 10a shows typical condensate connections. Figure
10b illustrates the internal trap for a typical vertical heat
pump. Each unit must be installed with its own individual
vent (where necessary) and a means to ush or blow out the
condensate drain line. Do not install units with a common
trap and/or vent.
Vent
*3/4" IPT
3/4" PVC
Alternate
Condensate
Location
Water
Connections
(21mm per m)
* Some units include a painted drain connection. Using a
threaded pipe or similar device to clear any excess paint
accumulated inside this fitting may ease final drain line installation.
Figure 10a: Vertical Condensate Drain
Figure 10b: Vertical Internal Condensate Trap
Section 10 - Packaged IOM 10 4/24/09 3:16:49 PM
Page view 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 49 50

Comments to this Manuals

No comments