ClimateMaster DC Series Installation Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
Residential H&V - 60Hz R22 &R410A
Rev.: 22 Dec, 2008
14
Water-Source Heating and Cooling Systems
Air Pad or
Extruded
polystyrene
insulation board
Unit Power
Disconnect
Thermostat
Wiring
Pressure
Tank
Shut-Off
Valve
Boiler
Drains
Flow
Regulator
Water In
Water Out
Water
Control
Valve
Optional
Filter
P/T Plugs
Figure 13: Typical Open Loop/Well Application
Ground-Water Heat Pump Applications
applications should be considered for the inherent energy
savings and smaller expansion tank requirements.
Water Control Valve
Note the placement of the water control valve in gure 13.
Always maintain water pressure in the heat exchanger by
placing the water control valve(s) on the discharge line
to prevent mineral precipitation during the off-cycle. Pilot
operated slow closing valves are recommended to reduce
water hammer. If water hammer persists, a mini-expansion
tank can be mounted on the piping to help absorb the excess
hammer shock. Insure that the total ‘VA’ draw of the valve
can be supplied by the unit transformer. For instance, a slow
closing valve can draw up to 35VA. This can overload smaller
40 or 50 VA transformers depending on the other controls
in the circuit. A typical pilot operated solenoid valve draws
approximately 15VA (see Figure 20). Note the special wiring
diagrams for slow closing valves (Figures 23 & 25).
Flow Regulation
Flow regulation can be accomplished by two methods. One
method of ow regulation involves simply adjusting the ball
valve or water control valve on the discharge line. Measure the
pressure drop through the unit heat exchanger, and determine
ow rate from tables 8a through 8c. Since the pressure is
constantly varying, two pressure gauges may be needed.
Adjust the valve until the desired ow of 1.5 to 2 gpm per ton
[2.0 to 2.6 l/m per kW] is achieved. A second method of ow
control requires a ow control device mounted on the outlet of
the water control valve. The device is typically a brass tting
with an ori ce of rubber or plastic material that is designed
to allow a speci ed ow rate. On occasion, ow control
devices may produce velocity noise that can be reduced by
applying some back pressure from the ball valve located on
the discharge line. Slightly closing the valve will spread the
pressure drop over both devices, lessening the velocity noise.
NOTE: When EWT is below 50°F [10°C], a minimum of 2
gpm per ton (2.6 l/m per kW) is required.
Water Coil Low Temperature Limit Setting
For all open loop systems the 30°F [-1.1°C] FP1 setting
(factory setting-water) should be used to avoid freeze
damage to the unit. See “Low Water Temperature Cutout
Selection” in this manual for details on the low limit setting.
CAUTION!
CAUTION! Refrigerant pressure activated water regulating
valves should never be used with ClimateMaster equipment.
CAUTION!
CAUTION! Units with ClimaDry Modulating Reheat option
installed in an open loop (well water) application require an
internal bronze pump. The cupro-nickel heat exchanger
option (which includes a bronze pump) must be used
for these applications. Failure to select this option could
result in premature equipment failure. ClimaDry is not
recommended for applications with poor water quality (see
water quality guidelines). The copper heat exchanger with
cast iron pump (standard ClimaDry option) is designed for
closed loop systems.
CAUTION!
CAUTION! Many units are installed with a factory or eld
supplied manual or electric shut-off valve. DAMAGE
WILL OCCUR if shut-off valve is closed during unit
operation. A high pressure switch must be installed on the
heat pump side of any eld provided shut-off valves and
connected to the heat pump controls in series with the
built-in refrigerant circuit high pressure switch to disable
compressor operation if water pressure exceeds pressure
switch setting. The eld installed high pressure switch shall
have a cut-out pressure of 300 psig and a cut-in pressure
of 250 psig. This pressure switch can be ordered from
ClimateMaster with a 1/4” internal are connection as part
number 39B0005N02.
Section 10 - Packaged IOM 14 4/24/09 3:16:50 PM
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 49 50

Comments to this Manuals

No comments