GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201310Test individual horizontal loop circuits before backfi lling. Test vertical U-bends and pond lo
11GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Flushing the Earth LoopFigure 8a: Valve Position A - Loop Fill/FlushLoopOutInValve PositionFig
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201312Figure 8b: Valve Position B - Unit Fill / FlushLoopValve PositionOutInFlushing the Earth LoopF
13GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 8e: Valve Position D - Pressurize and OperationLoopValve Position1Dead HeadPump toPress
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201314Multiple Unit Piping and FlushingOften projects require more than one heat pump. Where possib
15GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Multiple Unit Piping and FlushingWater OutWater InHeat PumpBWater OutWater InHeat PumpATo Grou
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201316Multiple Unit Piping and Flushing - Indoor Split (50YGS Only)Water OutWater InHeat PumpWater O
17GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Ground Loop Heat Pump Applications WARNING! Fluid Volume (gal [liters] per 100’ [30 meters)
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201318-50°F -40°F -30°F -20°F -10°F 0°F 10°F 20°F 30°F 40°F 50°F0.9600.9650.9700.9750.9800.9850.9900
19GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013High and Low Voltage KnockoutsVibration Isolation PadTo ThermostatInternal Motorized Modulatin
This page was intentionally left blank.
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201320High and Low Voltage KnockoutsVibration Isolation PadTo ThermostatInternal Motorized Modulatin
21GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Table 6: Water Quality StandardsWater QualityParameterHXMaterialClosedRecirculatingOpen Loop a
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201322Refrigeration Installation CAUTION! CAUTION! Installation of a factory supplied liquid line
23GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 14: Braze InstructionsTable 8: Service Valve PositionsFigure 15: Air Coil ConnectionTXV
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201324Refrigeration Installation° 3/4” Diameter suction lines: 1/4 lb. per foot of line set + 1 lb.
25GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Refrigeration Installationthe existing refrigerant fl ow control orifi ce or thermal expansion v
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201326Refrigeration InstallationFP2 Sensor InstallationAn FP2 sensor with violet wiring is shipped l
27GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 16b: Typical Split/Add-on Coil Fossil Fuel Furnace InstallationCompressor SectionTXV &a
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201328 NOTICE! NOTICE: Use tables 16a to 16d for superheat/subcooling values. These tables use di
29GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Hot Water GeneratorFigure 18: Typical HWG Installation(Indoor Compressor Section)Figure 19: HW
3GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Model Nomenclature: for Indoor Split Series5 = Motorized Valve (Modulating) Closed Loop Ap
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201330Hot Water Generator WARNING! WARNING! CHMWATER HEATERCHECK VALVE8” MAXHOT WATERTO HOUSEAN
31GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Hot Water GeneratorFor Indoor and Outdoor Compressor SectionTable 9: HWG Water Piping Size and
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201332Hot Water Generator Module Refrigeration InstallationFor Outdoor Compressor Section Only WARN
33GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Hot Water Generator Module Refrigeration InstallationOutdoor Compressor Section OnlyFully Insu
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201334Electrical - Line Voltage WARNING! CAUTION! Electrical - Line VoltageAll fi eld installed
35GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 22: Indoor Compressor Section (50YGS) Line Voltage Field WiringElectrical - Power Wirin
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201336Electrical - HWG WiringLow Voltage Field WiringELECTRICAL - LOW VOLTAGE WIRINGFigure 24: 50YGS
37GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Electrical - Thermostat WiringThermostat InstallationThe thermostat should be located on an in
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201338DXM2 Controls CAUTION! CAUTION! Do not restart units without inspection and remedy of faulti
39GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013DXM2 Layout and ConnectionsFigure 30: DXM2 Layout and ConnectionsLow Water Temperature Cutout
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 20134 WARNING! WARNING! CAUTION! SafetyWARNING! To avoid the release of refrigerant into the
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201340Indoor Split (50YGS) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N67
41GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Indoor Split (50YGS) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N67Low Voltage
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201342Outdoor Split (50YGP) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N66
43GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Outdoor Split (50YGP) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N66
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201344Indoor Split (50YGS) DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N68
45GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Indoor Split (50YGS) DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N68
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201346115V Hot Water Generator Kit (AHWG1BACS) Wiring Diagram - 96BN0141N1150YGP
47GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013230V Hot Water Generator Kit (AHWG1BGCS) Wiring Diagram - 96BN0141N1250YGP
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201348Unit Starting and Operating ConditionsCommissioning LimitsConsult Tables 13c - 13d for the par
49GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Unit Start-Up and Operating Conditions CAUTION! CAUTION! CAUTION! To avoid equipment dama
5GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013General InformationCAUTION! DO NOT store or install units in corrosive environments or in locat
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201350Unit Start-Up ProcedureSERVICE MODEMANUAL OPERATIONCONTROL DIAGNOSTICSDIPSWITCH CONFIGFAULT H
51GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Unit Operating ConditionsTable 15: Water Temperature Change Through Heat Exchanger9 - 1218 - 2
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201352Unit Operating ConditionsAntifreeze TypeAntifreeze %Cooling HeatingWPDCorr. Fct.EWT 30°F EWT 9
53GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Table 18a: Performance Data — 50YGS/50YGP Model 026 Full Load850 CFM Nominal (Rated) Airfl ow C
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201354Table 18b: Performance Data — 50YGS/50YGP Model 038 Full Load1250 CFM Nominal (Rated) Airfl ow
55GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Table 18c: Performance Data — 50YGS/50YGP Model 049 Full Load1500 CFM Nominal (Rated) Airfl ow
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201356Table 18d: Performance Data — 50YGS/50YGP Model 064 - Full Load1850 CFM Nominal (Rated) Airfl o
57GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Preventive MaintenanceWater Coil Maintenance (Direct ground water applicat
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201358TroubleshootingTable 19: Nominal resistance at various temperaturesTemp (ºC) Temp (ºF)Resista
59GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 20136Equipment SelectionThe installation of geothermal heat pump units and all associated components
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201360DXM2 Process Flow Chart WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER
61GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Functional TroubleshootingFault Htg Clg Possible Cause SolutionMain Power ProblemsX X Green st
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201362Performance TroubleshootingFunctional Troubleshooting (cont.)Unit PerformanceSentinel-Code 8X
63GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Symptom Htg Clg Possible Cause SolutionInsufficient Capacity/X X Dirty filter Replace or clean
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201364Performance Troubleshooting (cont.)Low Dischage AirTemperature in HeatingX Too high of air fl
65GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Troubleshooting FormRefrigerant Circuit DiagramNote: Never connect refrigerant gauges during s
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201366Warranty&$55,(5&25325$7,21/,0,7('(;35(66:$55$17</,0,7$7,212)5(0(',
67GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Notes
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201368Revision HistoryDate Page # Description29 Aug., 13 All First PublishedRMANUFACTURERCERTIFIEDTO
7GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Installation CAUTION! The installation of geothermal heat pump units and all associated compo
GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 20138Water ConnectionsThe TTS models utilize swivel piping fi ttings for water connections that are r
9GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Integrated Variable-Speed Water Flow Control Heat Pump Applications OverviewFigure 4a: Typical