ClimateMaster GT-PE outdoor Split Series Specifications

Browse online or download Specifications for Heat pumps ClimateMaster GT-PE outdoor Split Series. ClimateMaster GT-PE outdoor Split Series Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Table of Contents
Model Nomenclature 3
Safety 4
Storage 5
Pre-Installation 5
Equipment Selection 6
Installation 7-8
Water Connections 8
Integrated Variable-Speed 9
Water Flow Control
Heat Pump Applications Overview
Closed Loop Heat Pump Applications 10
with Internal Flow Controller
Flushing the Earth Loop 11-13
Multiple Unit Piping and Flushing 14-16
Ground Loop Heat Pump Applications 17-18
Closed Loop - External Central Pumping 19
Applications (Indoor 50YGS Only)
Open Loop or Ground-Water 20-21
Heat Pump Applications
Water Quality Standards 21
Lineset Information 22
Refrigeration Installation 22-28
Hot Water Generator 29-30
Hot Water Generator for Indoor and Outdoor 31
Compressor Section Only
Hot Water Generator 32-33
Module Refrigeration Installation
Outdoor Compressor Section Only
Electrical - Line Voltage 34
Electrical - Power Wiring 35
Electrical - HWG Wiring 36
Electrical - Low Voltage Wiring 36
Thermostat Wiring 37
DXM2 Controls 38
DXM2 Layout and Connections 39
Wiring Diagrams 40-47
Unit Start-Up and Operating Conditions 48-49
Unit Start-Up Procedure 49-50
Unit Operating Conditions 51-52
Performance Data 53-56
Preventive Maintenance 57
Troubleshooting 58-59
DXM2 Process Flow Chart 60
Functional Troubleshooting 61-62
Performance Troubleshooting 63-64
Troubleshooting Form 65
Warranty 66
Revision History 68
GT-PCS Digital Indoor Split Series (50YGS Models)
GT-PCS Digital Outdoor Split Series (50YGP Models)
Installation, Operation and Maintenance Instructions
Residential Split
Geothermal Heat Pumps
97B0048N06
Created: 29 Aug., 2013
Page view 0
1 2 3 4 5 6 ... 67 68

Summary of Contents

Page 1 - Table of Contents

Table of ContentsModel Nomenclature 3Safety 4Storage 5Pre-Installation 5Equipment Selection 6Installation 7-8Water Connections 8Integrated Variable

Page 2

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201310Test individual horizontal loop circuits before backfi lling. Test vertical U-bends and pond lo

Page 3 - 5 0 N0 2 6 2D 3 1

11GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Flushing the Earth LoopFigure 8a: Valve Position A - Loop Fill/FlushLoopOutInValve PositionFig

Page 4

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201312Figure 8b: Valve Position B - Unit Fill / FlushLoopValve PositionOutInFlushing the Earth LoopF

Page 5 - General Information

13GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 8e: Valve Position D - Pressurize and OperationLoopValve Position1Dead HeadPump toPress

Page 6 - Equipment Selection

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201314Multiple Unit Piping and FlushingOften projects require more than one heat pump. Where possib

Page 7 - Installation

15GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Multiple Unit Piping and FlushingWater OutWater InHeat PumpBWater OutWater InHeat PumpATo Grou

Page 8

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201316Multiple Unit Piping and Flushing - Indoor Split (50YGS Only)Water OutWater InHeat PumpWater O

Page 9

17GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Ground Loop Heat Pump Applications WARNING! Fluid Volume (gal [liters] per 100’ [30 meters)

Page 10 - Digital Pressure

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201318-50°F -40°F -30°F -20°F -10°F 0°F 10°F 20°F 30°F 40°F 50°F0.9600.9650.9700.9750.9800.9850.9900

Page 11 - Flushing the Earth Loop

19GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013High and Low Voltage KnockoutsVibration Isolation PadTo ThermostatInternal Motorized Modulatin

Page 12

This page was intentionally left blank.

Page 13

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201320High and Low Voltage KnockoutsVibration Isolation PadTo ThermostatInternal Motorized Modulatin

Page 14 - Created: 29 Aug., 2013

21GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Table 6: Water Quality StandardsWater QualityParameterHXMaterialClosedRecirculatingOpen Loop a

Page 15

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201322Refrigeration Installation CAUTION! CAUTION! Installation of a factory supplied liquid line

Page 16

23GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 14: Braze InstructionsTable 8: Service Valve PositionsFigure 15: Air Coil ConnectionTXV

Page 17 -  CAUTION! 

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201324Refrigeration Installation° 3/4” Diameter suction lines: 1/4 lb. per foot of line set + 1 lb.

Page 18

25GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Refrigeration Installationthe existing refrigerant fl ow control orifi ce or thermal expansion v

Page 19 - (Indoor Split 50YGS Only)

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201326Refrigeration InstallationFP2 Sensor InstallationAn FP2 sensor with violet wiring is shipped l

Page 20

27GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 16b: Typical Split/Add-on Coil Fossil Fuel Furnace InstallationCompressor SectionTXV &a

Page 21 - Corrosion Prevention

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201328 NOTICE! NOTICE: Use tables 16a to 16d for superheat/subcooling values. These tables use di

Page 22 - Refrigeration Installation

29GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Hot Water GeneratorFigure 18: Typical HWG Installation(Indoor Compressor Section)Figure 19: HW

Page 23

3GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Model Nomenclature: for Indoor Split Series5 = Motorized Valve (Modulating) Closed Loop Ap

Page 24

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201330Hot Water Generator WARNING!  WARNING! CHMWATER HEATERCHECK VALVE8” MAXHOT WATERTO HOUSEAN

Page 25

31GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Hot Water GeneratorFor Indoor and Outdoor Compressor SectionTable 9: HWG Water Piping Size and

Page 26

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201332Hot Water Generator Module Refrigeration InstallationFor Outdoor Compressor Section Only WARN

Page 27

33GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Hot Water Generator Module Refrigeration InstallationOutdoor Compressor Section OnlyFully Insu

Page 28

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201334Electrical - Line Voltage WARNING!  CAUTION! Electrical - Line VoltageAll fi eld installed

Page 29 - Hot Water Generator

35GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Figure 22: Indoor Compressor Section (50YGS) Line Voltage Field WiringElectrical - Power Wirin

Page 30

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201336Electrical - HWG WiringLow Voltage Field WiringELECTRICAL - LOW VOLTAGE WIRINGFigure 24: 50YGS

Page 31

37GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Electrical - Thermostat WiringThermostat InstallationThe thermostat should be located on an in

Page 32

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201338DXM2 Controls CAUTION! CAUTION! Do not restart units without inspection and remedy of faulti

Page 33 - Circulator

39GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013DXM2 Layout and ConnectionsFigure 30: DXM2 Layout and ConnectionsLow Water Temperature Cutout

Page 34 - Electrical - Line Voltage

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 20134 WARNING!  WARNING!  CAUTION! SafetyWARNING! To avoid the release of refrigerant into the

Page 35 - Electrical - Power Wiring

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201340Indoor Split (50YGS) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N67

Page 36 - Electrical - HWG Wiring

41GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Indoor Split (50YGS) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N67Low Voltage

Page 37

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201342Outdoor Split (50YGP) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N66

Page 38 - DXM2 Controls

43GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Outdoor Split (50YGP) DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N66

Page 39 - DXM2 Layout and Connections

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201344Indoor Split (50YGS) DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N68

Page 40

45GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Indoor Split (50YGS) DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N68

Page 41

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201346115V Hot Water Generator Kit (AHWG1BACS) Wiring Diagram - 96BN0141N1150YGP

Page 42

47GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013230V Hot Water Generator Kit (AHWG1BGCS) Wiring Diagram - 96BN0141N1250YGP

Page 43

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201348Unit Starting and Operating ConditionsCommissioning LimitsConsult Tables 13c - 13d for the par

Page 44

49GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Unit Start-Up and Operating Conditions CAUTION!  CAUTION! CAUTION! To avoid equipment dama

Page 45

5GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013General InformationCAUTION! DO NOT store or install units in corrosive environments or in locat

Page 46 - 96BN0141N11

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201350Unit Start-Up ProcedureSERVICE MODEMANUAL OPERATIONCONTROL DIAGNOSTICSDIPSWITCH CONFIGFAULT H

Page 47 - 96BN0141N12

51GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Unit Operating ConditionsTable 15: Water Temperature Change Through Heat Exchanger9 - 1218 - 2

Page 48

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201352Unit Operating ConditionsAntifreeze TypeAntifreeze %Cooling HeatingWPDCorr. Fct.EWT 30°F EWT 9

Page 49

53GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Table 18a: Performance Data — 50YGS/50YGP Model 026 Full Load850 CFM Nominal (Rated) Airfl ow C

Page 50 - Unit Start-Up Procedure

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201354Table 18b: Performance Data — 50YGS/50YGP Model 038 Full Load1250 CFM Nominal (Rated) Airfl ow

Page 51 - Unit Operating Conditions

55GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Table 18c: Performance Data — 50YGS/50YGP Model 049 Full Load1500 CFM Nominal (Rated) Airfl ow

Page 52

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201356Table 18d: Performance Data — 50YGS/50YGP Model 064 - Full Load1850 CFM Nominal (Rated) Airfl o

Page 53

57GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Preventive MaintenanceWater Coil Maintenance (Direct ground water applicat

Page 54

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201358TroubleshootingTable 19: Nominal resistance at various temperaturesTemp (ºC) Temp (ºF)Resista

Page 55

59GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE

Page 56

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 20136Equipment SelectionThe installation of geothermal heat pump units and all associated components

Page 57 - Preventive Maintenance

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201360DXM2 Process Flow Chart WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER

Page 58 - Troubleshooting

61GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Functional TroubleshootingFault Htg Clg Possible Cause SolutionMain Power ProblemsX X Green st

Page 59

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201362Performance TroubleshootingFunctional Troubleshooting (cont.)Unit PerformanceSentinel-Code 8X

Page 60 - Troubleshooting Flow Chart

63GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Symptom Htg Clg Possible Cause SolutionInsufficient Capacity/X X Dirty filter Replace or clean

Page 61 - Functional Troubleshooting

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201364Performance Troubleshooting (cont.)Low Dischage AirTemperature in HeatingX Too high of air fl

Page 62 - Performance Troubleshooting

65GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Troubleshooting FormRefrigerant Circuit DiagramNote: Never connect refrigerant gauges during s

Page 63

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201366Warranty&$55,(5&25325$7,21/,0,7('(;35(66:$55$17</,0,7$7,212)5(0(',

Page 64

67GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Notes

Page 65 - Troubleshooting Form

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 201368Revision HistoryDate Page # Description29 Aug., 13 All First PublishedRMANUFACTURERCERTIFIEDTO

Page 66 - Warranty

7GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Installation CAUTION! The installation of geothermal heat pump units and all associated compo

Page 67

GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 20138Water ConnectionsThe TTS models utilize swivel piping fi ttings for water connections that are r

Page 68 - *97B0048N06*

9GT-PCS Split Units - 60Hz Puron®Created: 29 Aug., 2013Integrated Variable-Speed Water Flow Control Heat Pump Applications OverviewFigure 4a: Typical