Functional Troubleshooting
Performance Troubleshooting
Fault Htg Clg Possible Cause Solution
Main power Problems X X Green Status LED Off Check Line Voltage circuit breaker and disconnect
Check for line voltage between L1 and L2 on the contactor
Check for 24VAC between R and C on CXM/DXM
Check primary/secondary voltage on transformer
HP Fault-Code 2 X Reduced or no water flow Check pump operation or valve operation/setting
High pressure in cooling
Check water flow adjust to proper flow rate
X
Water Temperature out of range in
cooling
Bring water temp within design parameters
X Reduced or no Air flow Check for dirty air filter and clean or replace
in heating Check fan motor operation and airflow restrictions
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table
X
Air Temperature out of range in
heating
Bring return air temp within design parameters
XX
Overcharged with refrigerant
Check superheat/subcooling vs typical operating condition
table
XX
Bad HP Switch Check switch continuity and operation. Replace
Performance
Troubleshooting
Htg Clg Possible Cause Solution
Insufficient capacity/ X X Dirty Filter Replace or clean
Not cooling or heating X Reduced or no Air flow Check for dirty air filter and clean or replace
properly in heating Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
X Reduced or no Air flow Check for dirty air filter and clean or replace
in cooling Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
X X Leaky duct work
Check supply and return air temperatures at the unit and at
distant duct registers if significantly different, duct leaks
are present
X X Low refrigerant charge Check superheat and subcooling per chart
X X Restricted metering device Check superheat and subcooling per chart. Replace.
X Defective Reversing Valve Perform RV touch test
X X Thermostat improperly located Check location and for air drafts behind stat
X X Unit undersized
Recheck loads & sizing check sensible clg load and heat
pump capacity
X X Scaling in water heat exchanger Perform Scaling check and clean if necessary
X X Inlet Water too Hot or Cold Check load, loop sizing, loop backfill, ground moisture.
High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace
in heating Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
X Reduced or no water flow Check pump operation or valve operation/setting
in cooling Check water flow adjust to proper flow rate
X Inlet Water too Hot Check load, loop sizing, loop backfill, ground moisture.
X
Air Temperature out of range in
heating
Bring return air temp within design parameters
X Scaling in water heat exchanger Perform Scaling check and clean if necessary
X X Unit Overcharged Check superheat and subcooling. Reweigh in charge
X X Non-condensables insystem Vacuum system and reweigh in charge
X X Restricted metering device Check superheat and subcooling per chart. Replace.
Low Suction Pressure X Reduced water flow Check pump operation or water valve operation/setting
in heating Plugged strainer or filter. Clean or replace.
Check water flow adjust to proper flow rate
X Water Temperature out of range Bring water temp within design parameters
X Reduced Air flow Check for dirty air filter and clean or replace
in cooling Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
X Air Temperature out of range
Too much cold vent air? Bring entering air temp within
design parameters
X X Insufficient charge Check for refrigerant leaks
Low discharge air
temperature in heating
X Too high of air flow Check fan motor speed selection and airflow chart
X Poor Performance See 'Insufficient Capacity'
High humidity X Too high of air flow Check fan motor speed selection and airflow chart
X Unit oversized
Recheck loads & sizing check sensible clg load and heat
pump capacity