Electrical - Line Voltage
CAUTION!
Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 4c: Genesis Packaged (GS) Series Electrical Data
Electrical - Line Voltage
All fi eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for
fuse sizes. Consult wiring diagram for fi eld connections that
must be made by the installing (or electrical) contractor.
All fi nal electrical connections must be made with a length of
fl exible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
ELECTRICAL - POWER WIRING
WARNING! Disconnect electrical power source to prevent
injury or death from electrical shock.
WARNING!
CAUTION!
Model
Compressor
HWG
Pump
FLA
Ext Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Min
AWG
Max Ft
(m)
RLA LRA Qty
PSC Electrical Data
015 6.1 29.0 1 0.4 4.0 1.0 11.5 13.0 15 12 56 (17.2)
018 7.7 38.0 1 0.4 4.0 1.0 13.1 15.0 20 12 77 (23.6)
024 10.3 56.0 1 0.4 4.0 1.1 15.8 18.4 25 10 100 (30.7)
030 12.2 67.0 1 0.4 4.0 1.3 17.9 21.0 30 10 88 (26.9)
036 13.5 73.0 1 0.4 4.0 1.8 19.7 23.1 35 10 80 (24.5)
042 16.5 95.0 1 0.4 4.0 1.9 22.8 26.9 40 10 69 (21.0)
048 18.3 109.0 1 0.4 4.0 3.0 25.7 30.3 45 8 97 (29.7)
060 25.0 148.0 1 0.4 4.0 3.4 32.8 39.1 60 8 75 (23.0)
070 28.8 148.0 1 0.4 4.0 4.9 38.1 45.3 70 6 103 (31.5)
ECM Electrical Data
015 6.1 29.0 1 0.4 4.0 5.0 15.5 17.0 20 12 68 (20.8)
018 7.7 38.0 1 0.4 4.0 5.0 17.1 19.0 25 12 97 (29.8)
024 10.3 56.0 1 0.4 4.0 5.0 19.7 22.3 30 10 83 (25.4)
030 12.2 67.0 1 0.4 4.0 5.0 21.6 24.7 35 10 75 (22.9)
036 13.5 73.0 1 0.4 4.0 5.0 22.9 26.3 35 10 70 (21.5)
042 16.5 95.0 1 0.4 4.0 5.0 25.9 30.0 45 10 61 (18.8)
048 18.3 109.0 1 0.4 4.0 7.4 30.1 34.7 50 8 85 (26.0)
060 25.0 148.0 1 0.4 4.0 7.4 36.8 43.1 60 6 108 (33.1)
070 28.8 148.0 1 0.4 4.0 7.4 40.6 47.8 70 6 98 (29.9)
Rated Voltage of 208/230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.