Electrical - Line Voltage
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect
switch and secure it in an open position during
installation.
CAUTION!
Use only copper conductors for eld installed
electrical wiring. Unit terminals are not designed to accept other
types of conductors.
Table 4a: Tranquility
27™ (TT) Series Electrical Data
Table 4b: Tranquility
20™ (TS) Series Electrical Data
WARNING! CAUTION!
All TT Units with ECM Fan Motor TT Units (ECM) Standard TT Units (ECM) with ClimaDry
Model
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Supply Wire
ClimaDry
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max/
Fuse
HACR
Supply Wire
RLA LRA Qty
Min
AWG
Max Ft
(m)
Min
AWG
Max Ft
(m)
026 10.3 52.0 1 0.40 4.0 4.3 19.0 21.6 30 10 86 (26.2) 0.8 19.8 22.4 30 10 82 (25.2)
038 16.7 82.0 1 0.40 4.0 4.3 25.4 29.6 45 10 63 (19.1) 0.8 26.2 30.4 45 8 97 (29.6)
049 21.2 96.0 1 0.40 4.0 7.0 32.6 37.9 50 8 78 (23.8) 1.07 33.7 39.0 60 8 76 (23.1)
064 25.6 118.0 1 0.40 4.0 7.0 37.0 43.4 60 6 108 (32.9) 1.07 38.1 44.5 70 6 105 (32.1)
072 27.2 150.0 1 0.40 4.0 7.0 38.6 45.4 70 66 103 (31.4) 1.07 39.6 46.4 70 6 101 (30.8)
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
Standard TS Unit TS Unit with ClimaDry
Model
Compressor
HWG
Pump
FLA
Ext
Loop
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Cir-
cuit
Amps
Max
Fuse/
HACR
Supply Wire
ClimaDry
Pump
FLA
Total
Unit
FLA
Min
Cir-
cuit
Amps
Max
Fuse/
HACR
Supply Wire
RLA LRA Qty
Min
AWG
Max Ft
(m)
Min
AWG
Max Ft
(m)
PSC Electrical Data
018 9.0 48.0 1 0.40 4.0 1.0 14.4 16.7 25 0.8 15.2 17.5 25
024 12.8 60.0 1 0.40 4.0 1.1 18.3 21.5 30 10 86 (26.3) 0.8 19.1 22.3 35 10 83 (25.4)
030 13.5 61.0 1 0.40 4.0 1.4 19.3 22.7 35 10 81 (24.9) 0.8 20.1 23.5 35 10 78 (24.1)
036 14.7 72.5 1 0.40 4.0 2.1 21.2 24.9 35 10 74 (22.7) 0.8 22.0 25.7 40 10 72 (22.0)
042 15.4 83.0 1 0.40 4.0 2.1 21.9 25.8 40 10 72 (21.9) 0.8 22.7 26.6 40 10 70 (21.3)
048 20.5 109.0 1 0.40 4.0 3.0 27.9 33.0 50 8 90 (27.3) 1.07 29.0 34.1 50 8 87 (26.4)
060 26.9 145.0 1 0.40 4.0 4.9 36.2 42.9 60 6 109 (33.3) 1.07 37.3 44.0 70 6 106 (32.4)
070 30.1 158.0 1 0.40 4.0 5.8 40.3 47.8 70 6 98 (29.9) 1.07 41.4 48.9 70 6 96 (29.2)
ECM Electrical Data
018 9.0 48.0 1 0.40 4.0 4.3 17.7 20.0 25 0.8 18.5 20.8 25
024 12.8 60.0 1 0.40 4.0 4.3 21.5 24.7 35 10 75 (22.9) 0.8 22.3 25.5 35 10 72 (22.2)
030 13.5 61.0 1 0.40 4.0 4.3 22.2 25.6 35 10 72 (22.1) 0.8 23.0 26.4 35 10 70 (21.4)
036 14.7 72.5 1 0.40 4.0 4.3 23.4 27.1 40 10 69 (20.9) 0.8 24.2 27.9 40 10 66 (20.3)
042 15.4 83.0 1 0.40 4.0 4.3 24.1 27.9 40 10 66 (20.2) 0.8 24.9 28.8 40 10 64 (19.6)
048 20.5 109.0 1 0.40 4.0 7.0 31.9 37.0 50 8 80 (24.5) 1.07 33.0 38.1 50 8 78 (23.7)
060 26.9 145.0 1 0.40 4.0 7.0 38.3 45.0 70 6 104 (31.7) 1.07 39.4 46.1 70 6 101 (31.9)
070 30.1 158.0 1 0.40 4.0 7.0 41.5 49.0 70 6 96 (29.1) 1.07 42.6 50.1 80 6 93 (28.5)
Rated Voltage of 208-230/60/1 Min/Max Voltage of 197/254
HACR circuit breaker in USA only All fuses Class RK-5
Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor and Minimum Circuit Ampacity.
Section 10 - Packaged IOM 18 4/24/09 3:16:50 PM