ClimateMaster DC Series Installation Manual Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
Residential H&V - 60Hz R22 &R410A
Rev.: 22 Dec, 2008
24
Water-Source Heating and Cooling Systems
ECM Blower Control
The ECM fan is controlled by an interface board that
converts thermostat inputs and eld selectable CFM
settings to signals used by the ECM motor controller.
Units manufactured before July 2005 have version I (P/N
69243707). Units manufactured after July 2005 have version
II (P/N 17B0019N01). Fan speeds are selected with jumpers
for version I or via a nine position DIP switch for version II.
To take full advantage of the ECM motor features, a multi-
stage thermostat should be used (2-stage heat/2-stage
cool or 3-stage heat/2-stage cool).
Note: Power must be off to the unit for at least three
seconds before the ECM motor will recognize a speed
change. The motor will recognize a change in the CFM
Adjust or dehumidi cation mode settings while the unit is
powered.
There are four different air ow settings from lowest air ow
rate (speed tap 1) to the highest air ow rate (speed tap 4).
The charts below indicate settings for both versions of the
ECM interface board, followed by detailed information for
each setting.
Cooling Settings: The cooling setting determines the
cooling (normal) CFM for all units with ECM motor.
Cooling (normal) setting is used when the unit is not in
dehumidi cation mode. This setting also determines the
heating CFM for Genesis (GS) units. Tap 1 is the lowest
CFM setting, while tap 4 is the highest CFM setting. To
avoid air coil freeze-up, tap 1 may not be used if the
dehumidi cation mode is selected. Consult submittal data
or speci cations catalog for the speci c unit series and
model to correlate speed tap setting to air ow in CFM.
Heati
ng Settings
: The heating setting determines the
heating CFM for Tranquility 27™ (TT) and Tranquility 20™
(TS) units. This setting is not used for Genesis (GS) units.
Tap 1 is the lowest CFM setting, while tap 4 is the highest
CFM setting. Consult submittal data or speci cations
catalog for the speci c unit series and model to correlate
speed tap setting to air ow in CFM.
Auxiliary/Emergency Heat Settings: The auxiliary/
emergency heat setting determines the CFM when the unit
is in auxiliary heat or emergency heat mode. This setting
is used for residential units with internal electric heat.
When auxiliary electric heat is energized (i.e. compressor
and electric heat), the greater of the auxiliary/emergency
or heating setting will be used. A “G” (fan) signal must be
present from the thermostat for electric heat to operate.
Consult the submittal data or speci cations catalog for the
speci c unit series and model to correlate speed tap setting
to air ow in CFM.
CFM Adjust Settings: The CFM adjust setting allows
four selections. The NORM setting is the factory default
position. The + or – settings adjust the air ow by +/- 15%.
The +/- settings are used to “ ne tune” air ow adjustments.
The TEST setting runs the ECM motor at 70% torque, which
causes the motor to operate like a standard PSC motor, and
disables the CFM counter.
Dehumidi cation Mode Settings: The dehumidi cation
mode setting provides eld selection of humidity control.
When operating in the normal mode, the cooling air ow
settings are determined by the cooling tap setting above.
When dehumidi cation is enabled there is a reduction in
air ow in cooling to increase the moisture removal of the
heat pump. Consult submittal data or speci cations catalog
for the speci c unit series and model to correlate speed
tap to air ow in CFM. The dehumidi cation mode can be
enabled in two ways.
1. Constant Dehumidi cation Mode: When the
dehumidi cation mode is selected (via DIP switch or
jumper setting), the ECM motor will operate with a
multiplier applied to the cooling CFM settings (approx.
20-25% lower air ow). Any time the unit is running in
the cooling mode, it will operate at the lower air ow
to improve latent capacity. The “DEHUM” LED will be
illuminated at all times. Heating air ow is not affected.
NOTE: Do not select dehumidi cation mode if cooling
setting is tap 1.
2. Automatic (Humidistat-controlled) Dehumidi cation
Mode: When the dehumidi cation mode is selected
(via DIP switch or jumper setting) AND a humidistat is
connected to terminal DH (version II) or HUM (version
I), the cooling air ow will only be reduced when the
humidistat senses that additional dehumidi cation is
required. The DH (or HUM) terminal is reverse logic.
Therefore, a humidistat (not dehumidistat) is required.
The “DEHUM” LED will be illuminated only when
the humidistat is calling for dehumidi cation mode.
Heating air ow is not affected. NOTE: Do not select
dehumidi cation mode if cooling setting is tap 1.
Section 10 - Packaged IOM 24 4/24/09 3:16:52 PM
Page view 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 49 50

Comments to this Manuals

No comments