ClimateMaster AG series Specifications Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
TT
56
Tranquility
27™ (TT) Series
ClimateMaster: Smart. Responsible. Comfortable.
AHRI/ISO/ASHRAE/ANSI 13256-1 Performance
ASHRAE/AHRI/ISO 13256-1. English (IP) Units
ASHRAE/AHRI/ISO 13256-1. Metric (SI) Units
Model
Capacity
Modulation
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F
Cooling
Full Load 77°F
Part Load 68°F
Heating
Full Load 32°F
Part Load 41°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
026
Full 25,300 15.9 30,800 5.3 28,900 24.5 25,700 4.8 26,600 18.5 19,800 4.0
Part 19,400 18.3 22,400 6.1 22,200 30.8 18,600 5.1 21,300 26.0 16,500 4.6
038
Full 36,200 15.6 44,800 5.3 41,200 23.0 36,700 4.7 38,200 18.2 29,000 4.0
Part 26,200 18.5 30,800 6.3 30,200 31.5 24,800 5.1 28,900 27.0 22,100 4.5
049
Full 48,400 15.7 59,900 5.2 54,600 22.5 48,300 4.7 50,600 17.9 37,500 4.0
Part 36,100 18.0 44,300 6.2 40,700 28.7 35,400 5.1 39,600 24.9 31,200 4.6
064
Full 61,500 15.0 72,300 5.0 68,600 22.0 59,600 4.4 64,800 17.5 48,000 3.9
Part 44,900 17.6 51,100 5.7 51,900 29.7 41,800 4.7 49,800 25.3 37,500 4.3
072
Full 68,700 14.2 88,600 4.9 77,100 19.9 70,200 4.3 71,600 16.2 54,100 3.6
Part 52,800 16.0 65,200 5.1 59,800 24.5 51,700 4.3 57,700 21.4 45,400 3.9
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
Ground Loop Heat Pump ratings based on 15% methanol antifreeze solution
All ratings based upon operation at lower voltage of dual voltage rated models
Model
Capacity
Modulation
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C
Cooling
Full Load 25°C
Part Load 20°C
Heating
Full Load 0°C
Part Load 5°C
Capacity
Watts
EER
W/W
Capacity
Watts
COP
Capacity
Watts
EER
W/W
Capacity
Watts
COP
Capacity
Watts
EER
W/W
Capacity
Watts
COP
026
Full 7,415 4.7 9,027 5.3 8,470 7.2 7,532 4.8 7,796 5.4 5,803 4.0
Part 5,686 5.4 6,565 6.1 6,506 9.0 5,451 5.1 6,243 7.6 4,836 4.6
038
Full 10,610 4.6 13,130 5.3 12,075 6.7 10,756 4.7 11,196 5.3 8,499 4.0
Part 7,679 5.4 9,027 6.3 8,851 9.2 7,268 5.1 8,470 7.9 6,477 4.5
049
Full 14,185 4.6 17,556 5.2 16,002 6.6 14,156 4.7 14,830 5.2 10,991 4.0
Part 10,580 5.3 12,984 6.2 11,928 8.4 10,375 5.1 11,606 7.3 9,144 4.6
064
Full 18,025 4.4 21,190 5.0 20,106 6.4 17,468 4.4 18,992 5.1 14,068 3.9
Part 13,159 5.2 14,977 5.7 15,211 8.7 12,251 4.7 14,596 7.4 10,991 4.3
072
Full 20,135 4.2 25,967 4.9 22,597 5.8 20,574 4.3 20,985 4.7 15,856 3.6
Part 15,475 4.7 19,109 5.1 17,526 7.2 15,152 4.3 16,911 6.3 13,306 3.9
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
Ground Loop Heat Pump ratings based on 15% methanol antifreeze solution
All ratings based upon operation at lower voltage of dual voltage rated models
Page view 7