ClimateMaster OD Series Specifications Page 39

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 38
ClimateMaster works continually to improve its products. As a result, the design and speci cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for speci c information on the current design and speci cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Revised: 16 December, 2014LC994 - 39
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P
TSM Non Ducted ECM 88 and 80" Cabinets
ECM Blower Performance Data
Constant
Tranquility
Model
ESP
Range
(in wg)
Range
Cooling Mode Dehumid Mode Heating Mode
Fan Only
Mode
Hi Fan
Mode
Aux
Emerg
Mode
Stg 2 Stg 1 Stg 2 Stg 1 Stg 2 Stg 1
TSM09 0 to 0.25
Default 400 350 350 300 450 400 300 400 450
Maximum 500 500 500 500 500 500 500 500 500
Minimum 300 300 300 300 300 300 300 300 400
TSM12 0 to 0.25
Default 450 400 400 350 450 400 300 400 450
Maximum 500 500 500 500 500 500 500 500 500
Minimum 300 300 300 300 300 300 300 300 400
TSM15 0 to 0.3
Default 700 600 600 500 600 500 500 600 600
Maximum 700 700 700 700 700 700 700 700 700
Minimum 500 500 500 500 500 500 500 500 500
TSM18 0 to 0.3
Default
700 600 600 500 700 600 500 600 600
Maximum 800 800 800 800 800 800 800 800 800
Minimum 500 500 500 500 500 500 500 500 500
TSM24 0 to 0.3
Default 850 750 750 650 750 650 600 750 750
Maximum 950 950 950 950 950 950 950 950 950
Minimum 650 650 600 600 600 600 600 600 600
TSM30 0 to 0.4
Default 1100 1000 1000 900 1100 1000 700 850 1000
Maximum 1100 1000 1100 900 1100 1100 1100 1100 1100
Minimum 900 850 800 800 900 900 700 700 900
TSM36 0 to 0.4
Default 1200 1100 1100 1000 1200 1100 900 950 1350
Maximum 1350 1350 1350 1350 1350 1350 1350 1350 1350
Minimum 1100 1100 1100 1000 900 900 900 900 1000
All data wet coil clean lter.
All units AHRI/ISO/ASHRAE 13256-1 rated on CFM shown on performance data page.
Air ow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Shipped on default settings. C = Cooling; H = Heating; D = Dehumidi cation.
Change from default setting with service tool (ACDU02) or Communicating thermostat (ATC32U01).
Air ow is controlled within 7% up to the max ESP with recommended supply air openings and sizes (See SA Grille Table).
TRM15-36 ramp default is 30.